Haoguang LSZH shielded fire resistant multi core alarm cable often used in building Management Systems(BMS),control and instrumentation, like voice alarm systems, emergency and escape lighting and other essential service control circuits. This product is manufactured with latest technology to ensure consistent quality and reliability. We use good quality solid bare copper conductor,top quality insulation,LSZH sheath material(Low Smoke Zero Halogen). The range of products includes flame retardant cables. Welcome to inquiry.
1.Product Introduction of LSZH Shielded Fire Resistant Multi Core Alarm Cable
This LSZH shielded Fire Resistant Alarm cables multi core alarm cable is manufactured with latest technology to ensure consistent quality and reliability. We use good quality ceramifiable silicone rubber insulation and pure copper and LSZH sheath material( Low Smoke Zero Halogen). We use eco-friendly materials,RoHS compliance. This cable intend to assure service during a fire but are chosen to prevent the flame spreading,offer continued functionality of critical systems in the event of fire.
Application :
LSZH sheath Fire Resistant Alarm cables (2 cores or more )often used in building Management Systems(BMS),control and instrumentation, like voice alarm systems, emergency and escape lighting and other essential service control circuits. Fire protection system,emergency lights,sprinklers,ventilation devices,smoke alarm,emergency lighting system,fire alarm system.
2.Product Parameter (Specification) of LSZH Shielded Fire Resistant Multi Core Alarm Cable.
Max Operating voltage: 300/500V
Operating Temperature: from -20℃ to 90℃
Part Number |
Number of Cores |
Conductor Cross Section sqmm |
Conductor Construction mm |
Nom.Insulation Thickness mm |
Nom.Insulation Diameter mm |
Nom.Drain Wire Cross Section Thickness sqmm |
Nom.Sheath Thickness mm |
Nom.Overall Diameter mm |
H210 |
2 |
1.00 |
1x1.13 |
0.7 |
2.5 |
|
0.8 |
6.7 |
H210S |
2 |
1.00 |
1x1.13 |
0.7 |
2.5 |
0.50 |
0.8 |
6.8 |
H215 |
2 |
1.50 |
1x1.38 |
0.7 |
2.8 |
|
1.2 |
8.1 |
H215S |
2 |
1.50 |
1x1.38 |
0.7 |
2.8 |
0.50 |
1.2 |
8.2 |
H225 |
2 |
2.5 |
1x1.78 |
0.8 |
3.4 |
|
1.2 |
9.3 |
H225S |
2 |
2.5 |
1x1.78 |
0.8 |
3.4 |
0.50 |
1.2 |
9.4 |
3. Product Feature of LSZH Shielded Fire Resistant Multi Core Alarm Cable.
1) Conductor: Solid bare copper. We supply 2 core or more fire alarm cables.
2) Insulation: Ceramifiable Silicone rubber
3) Insulation Colour: Blue(core 1), Brown(core 2)
4) Drain wire(if applicable): Solid Tinned or Bare flexible copper.
5) Wrapping tape(if applicable): Polyester tape.
6) Screen (if applicable): Aluminium/Polyester tape.
7) Sheath Material: LSZH.
4 Product Details of LSZH Shielded Fire Resistant Multi Core Alarm Cable.
1) High quality and Eco-friendly material.
2) Flexible order quantity. We can supply the cable to meet customer's requirement. But if we have stock,even 1 coil is acceptable for shipping.
3) Long lasting stability.
4) We have exported our cable to many countries.
5) LSZH = low smoke zero halogen = low smoke halogen free.
6) Brand: Haoguang. Made in China.
5 Packaging & Delivery
1) Packaging Details:
It is determined by the quantity and requirements you purchase. Can be negotiated. Wood roll, Wood pallet, PE firm wrapped.
2) Port: Ningbo,Shanghai
3)Delivery: By Sea, By Train, By Air, By express.
6 FAQ:
1)Are you a manufacturer or trading company?
We are a professional manufacturer. We can control your order from the first beginning to the last. Because we are the factory.
2)Can I order the cable/wire which is lower than your MOQ?
First, we will check the inventory.if it is in stock, sure, it’s ok! But if it was out of stock, when your quantity is close to our MOQ, it’s OK. If it is much less than MOQ, maybe we will take it as a sample order, the price will be different.
3) Are samples free shipping?
Sorry, it should be on customer side.
4) What is spark test?
A spark test is an inline voltage test used either during cable manufacturing or during a rewinding process. Spark testing is primarily for low voltage insulations and medium voltage non-conducting jacket or sheaths. The test unit generates an electrical cloud around the cable which in high frequency AC units appears as a blue corona around the cable. Any pin holes or faults in the insulation will cause a grounding of the electrical field and this flow of current is used to register an insulation fault.
5)What is Fire resistant (fire rated) cables?
Fire resistant cable continues to operate in the presence of fire, hence their reference as Circuit Integrity cables, This includes PH30, PH60 and PH120 cables.